前言:想要寫出一篇令人眼前一亮的文章嗎?我們特意為您整理了5篇節(jié)能項(xiàng)目范文,相信會(huì)為您的寫作帶來幫助,發(fā)現(xiàn)更多的寫作思路和靈感。
1、LED節(jié)能燈是繼緊湊型熒光燈(即普通節(jié)能燈)后的新一代照明光源,LED節(jié)能燈環(huán)保不含汞,可回收再利用,功率小,高光效,長(zhǎng)壽命,即開即亮,耐頻繁開關(guān),光衰小,色彩豐富,可調(diào)光,變幻豐富。
2、LED即半導(dǎo)體發(fā)光二極管,是一種固態(tài)的半導(dǎo)體器件,它可以直接把電轉(zhuǎn)化為光。LED節(jié)能燈是用高亮度白色發(fā)光二極管發(fā)光源,光效高、耗電少,壽命長(zhǎng)、易控制、免維護(hù)、安全環(huán)保;是新一代固體冷光源,光色柔和、艷麗、豐富多彩、低損耗、低能耗,綠色環(huán)保,適用家庭,商場(chǎng),銀行,醫(yī)院,賓館,飯店其他各種公共場(chǎng)所長(zhǎng)時(shí)間照明。
3、LED光源是21世紀(jì)光源市場(chǎng)的希望,眾多優(yōu)點(diǎn)預(yù)告其未來將逐步取代傳統(tǒng)光源,奧科委指出高亮度LED將是人類繼愛迪生發(fā)明白熾燈泡之后,最偉大的發(fā)明之一,當(dāng)前全球能源危機(jī)的時(shí)候,能源是一種寶貴的資源,所以節(jié)約能源是我們未來面臨的問題。LED作為一種新型的節(jié)能、環(huán)保的綠色光源產(chǎn)品,必然是未來發(fā)展的趨勢(shì)。
(來源:文章屋網(wǎng) )
Abstracts:Clean purification plant purifying air conditioning system, larger area, purification level requirements are relatively high, in the general design, the majority of the secondary return air system, outdoor fresh air and indoor air after cooling section and a heating section, and the air conditioning unit sizes larger, so that the consumption of cooling and heating energy consumption has increased, equipment and construction costs and operating costs also increased; the two return air system design, return air in the cooling section after the accession, the air conditioning unit consumption of cooling capacity and heating capacity is reduced, equipment ( cooling device, such as a motor ) investment and operating cost are reduced correspondingly, design not only can satisfy the temperature humidity and cleanliness requirements, but also saves the energy consumption. In this paper, a project of clean workshop as an example, analysis using two primary return air system of energy saving about 20% the left and right sides, draw conclusions from the large supply air volume, air purification project, the two return air system than the secondary return air system in energy-saving aspects to winning more.
關(guān)鍵詞:節(jié)能回風(fēng)利用
Key words:Energy use of return air
中圖分類號(hào):TE08 文獻(xiàn)標(biāo)識(shí)碼:A文章編號(hào):
1、引言
在潔凈室空氣調(diào)節(jié)設(shè)計(jì)中,我們往往強(qiáng)調(diào)空氣凈化品質(zhì)和氣流組織形式的控制,而忽略了空氣處理過程、合理利用回風(fēng)等諸多方面的節(jié)能設(shè)計(jì)。隨著潔凈室建造規(guī)模迅速發(fā)展和擴(kuò)大,設(shè)計(jì)中的節(jié)能問題引起高度重視。在潔凈室設(shè)計(jì)中應(yīng)采用先進(jìn)的節(jié)能技術(shù)和措施,精心設(shè)計(jì),達(dá)到節(jié)能目的。
2、工程概況
上海浦東某項(xiàng)目是以1-7#樓和變電房8個(gè)單體建筑物構(gòu)成,其中綜合樓為九層,1-6#樓為5層,總建筑面積約100000m2,該項(xiàng)目機(jī)電安裝工程由管道工程、電氣工程、通風(fēng)空調(diào)工程及弱電工程組成。本工程以每個(gè)建筑單位為單體,設(shè)置集中空調(diào)冷暖源和潔凈車間的凈化空調(diào)系統(tǒng)。
該項(xiàng)目5#樓凈化車間位于5#樓底層,分別由實(shí)驗(yàn)室等幾個(gè)潔凈空間組成,總面積5000多m2。整個(gè)系統(tǒng)(包含非凈化區(qū))有30臺(tái)空調(diào)機(jī)組和新風(fēng)機(jī)組。
結(jié)合本項(xiàng)目的實(shí)施,就凈化空調(diào)系統(tǒng)的節(jié)能回風(fēng)能耗利用進(jìn)行探討。
2.1凈化空調(diào)系統(tǒng)的主要特點(diǎn)
(1)根據(jù)國(guó)家標(biāo)準(zhǔn)《潔凈廠房設(shè)計(jì)規(guī)范》(GB50073-2001)(以下簡(jiǎn)稱《規(guī)范》)第6.1.4條的
規(guī)定,生產(chǎn)工藝無(wú)要求的潔凈室夏季室內(nèi)設(shè)計(jì)參數(shù):溫度:24℃~26℃,濕度:50%~70%。冬季室內(nèi)設(shè)計(jì)參數(shù):溫度:20℃~22℃,濕度:30%~50%。很多生產(chǎn)車間對(duì)凈化空調(diào)系統(tǒng)溫濕度及精度要求并不高,有些生產(chǎn)車間關(guān)鍵生產(chǎn)環(huán)節(jié)的要求較高,而其他輔助區(qū)的要求相對(duì)較低。根據(jù)《規(guī)范》第6.1.3條,某些項(xiàng)目生產(chǎn)工藝對(duì)室內(nèi)的溫、濕度及其允許波動(dòng)的范圍具有較高要求,宜單獨(dú)設(shè)置空調(diào)系統(tǒng)。
(2)空氣凈化系統(tǒng)是潔凈室中主要能耗部分,主要表現(xiàn)在兩個(gè)方面,其一是制冷負(fù)荷,其二是風(fēng)機(jī)等的運(yùn)行負(fù)荷。制冷負(fù)荷主要由新風(fēng)負(fù)荷、工藝設(shè)備負(fù)荷、圍護(hù)結(jié)構(gòu)負(fù)荷等形成,并以新風(fēng)負(fù)荷最大,而工藝設(shè)備和圍護(hù)結(jié)構(gòu)的冷負(fù)荷相對(duì)穩(wěn)定且較小。運(yùn)行負(fù)荷主要由于潔凈室要求的大風(fēng)量、高風(fēng)壓形成。根據(jù)《規(guī)范》第6.3.3條,為保證空氣潔凈等級(jí),6級(jí)時(shí)換氣次數(shù)取50~60次,7級(jí)時(shí)換氣次數(shù)取15~25次,某些負(fù)荷較大的房間還需增加換氣次數(shù)??照{(diào)系統(tǒng)的送風(fēng)溫差由熱濕負(fù)荷與送風(fēng)量決定, 因此凈化空調(diào)的送風(fēng)溫差要比舒適性空調(diào)小很多。
(3)在某些行業(yè)的潔凈廠房中,潔凈走廊等很多功能房間僅照明、圍護(hù)結(jié)構(gòu)形成熱負(fù)荷,濕負(fù)荷很小。而某些房間設(shè)備和人員相對(duì)集中,房間余熱余濕相對(duì)較大,經(jīng)綜合經(jīng)濟(jì)比較后,室內(nèi)空氣仍應(yīng)循環(huán)使用。這個(gè)特點(diǎn)有利于我們區(qū)別各個(gè)房間的回風(fēng)狀態(tài),合理進(jìn)行處理或利用。
在工作中,我們注意到,有些潔凈廠房具備上述特點(diǎn),但設(shè)計(jì)中空氣處理過程仍然采用一次回風(fēng)系統(tǒng),這樣設(shè)計(jì)的結(jié)果,造成冷負(fù)荷增大,制冷系統(tǒng)一次性投資加大,空調(diào)系統(tǒng)運(yùn)行費(fèi)用增高。
針對(duì)其中某車間分析,室內(nèi)冷負(fù)荷90kW,濕負(fù)荷36kg/h,室外計(jì)算干球溫度33.5℃,濕球溫度27.7℃,新風(fēng)量4000m3/h,室內(nèi)設(shè)計(jì)溫度26℃,相對(duì)濕度60%。
根據(jù)以往的類似工程實(shí)踐經(jīng)驗(yàn),結(jié)合該潔凈車間的實(shí)際條件,我們認(rèn)為:該潔凈車間,面積較大、溫濕度要求不是很高,凈化級(jí)別要求相對(duì)較高的廠房類凈化工程,二次回風(fēng)系統(tǒng)足以滿足要求。設(shè)計(jì)中如果采用一次回風(fēng)系統(tǒng),不但加大了初期投資費(fèi)用,而且日后的運(yùn)行費(fèi)用也增大了。
2.2一次回風(fēng)系統(tǒng)和二次回風(fēng)系統(tǒng)的能耗進(jìn)行比較
現(xiàn)根據(jù)回風(fēng)流程圖來對(duì)一次回風(fēng)系統(tǒng)和二次回風(fēng)系統(tǒng)的比較分析:
(1)在夏季和接近夏季的過渡季節(jié)工況下,一次回風(fēng)系統(tǒng)空氣處理流程圖見圖1,新風(fēng)與回風(fēng)混合后,經(jīng)表冷器冷卻到“機(jī)器露點(diǎn)”,然后再利用電能或者蒸汽加熱后送入室內(nèi)。一次回風(fēng)系統(tǒng)空氣處理h-d工況見圖2。
圖1一次回風(fēng)空氣處理流程圖
圖2一次回風(fēng)空氣處理焓濕圖
(2)夏季空氣處理過程采用固定二次回風(fēng)系統(tǒng),減少在同一空調(diào)系統(tǒng)中同時(shí)加熱和冷卻,達(dá)到節(jié)能目的。
根據(jù)凈化車間工藝生產(chǎn)流程的特點(diǎn),我們提出以下兩種形式的二次回風(fēng)系統(tǒng)。第一種為集中回風(fēng)型二次回風(fēng)系統(tǒng),空氣處理流程圖見圖3。凈化車間的回風(fēng)集中回至空調(diào)機(jī)房后分為一次與二次回風(fēng)。新風(fēng)與一次回風(fēng)混合后,經(jīng)表冷器冷卻到“機(jī)器露點(diǎn)”,再與二次回風(fēng)混合,代替二次加熱(后面的加熱段為冬季用)。這一種二次回風(fēng)系統(tǒng)適用于生產(chǎn)車間沒有很大的散熱散濕工藝設(shè)備,各個(gè)房間的熱濕比線差別不大的潔凈廠房。優(yōu)點(diǎn)是回風(fēng)管路簡(jiǎn)單,一次投資較少。第二種二次回風(fēng)系統(tǒng)為獨(dú)立回風(fēng)型二次回風(fēng)系統(tǒng),空氣處理流程圖見圖4,熱濕負(fù)荷相對(duì)較大的房間獨(dú)立回風(fēng),接至空調(diào)機(jī)組一次回風(fēng)段,熱負(fù)荷穩(wěn)定且濕負(fù)荷較小的房間獨(dú)立回風(fēng),接至空調(diào)機(jī)組的二次回風(fēng)段。這一種二次回風(fēng)系統(tǒng)適用于各個(gè)房間的熱濕比線差別較大的潔凈廠房,其優(yōu)點(diǎn):①充分利用了空調(diào)機(jī)組的降溫除濕功能。②一次回風(fēng)與二次回風(fēng)的壓差可以通過管路平衡。缺點(diǎn)是管路系統(tǒng)復(fù)雜,計(jì)算復(fù)雜。
圖3集中回風(fēng)型二次回風(fēng)空氣處理流程圖
圖4 獨(dú)立回風(fēng)型二次回風(fēng)空氣處理流程圖
集中回風(fēng)型二次回風(fēng)系統(tǒng)空氣處理h-d工況見圖5。相對(duì)一次回風(fēng)系統(tǒng)送風(fēng)溫差tn-to不變,二次回風(fēng)代替二次加熱,避免的冷熱相抵。S點(diǎn)為一次混合冷卻處理后L1點(diǎn)與二次回風(fēng)N點(diǎn)的混合點(diǎn),因此三點(diǎn)必在一條直線上,二次混風(fēng)比與一次混風(fēng)比即可確定。一次混風(fēng)C1點(diǎn)向室外點(diǎn)W靠近,二次回風(fēng)系統(tǒng)機(jī)器露點(diǎn)L1點(diǎn)較一次回風(fēng)系統(tǒng)低,因此表冷器處理的空氣焓差增大,機(jī)器露點(diǎn)L1降低,制冷系統(tǒng)效率相對(duì)降低。
圖5 集中回風(fēng)型二次回風(fēng)空氣處理焓濕圖
圖6 獨(dú)立回風(fēng)型二次回風(fēng)空氣處理焓濕圖
獨(dú)立回風(fēng)型二次回風(fēng)系統(tǒng)空氣處理h-d工況見圖6。O點(diǎn)空氣送入不同的房間,經(jīng)不同的熱濕比線到點(diǎn)N1、N2,N1作為一次回風(fēng)與W混合,N2作為二次回風(fēng)與L1’混合。與集中回風(fēng)型二次回風(fēng)相比,N、N1、N2三點(diǎn)在一條支線上,一次混風(fēng)C1’點(diǎn)向室外點(diǎn)W靠近,L1’相對(duì)L1有所提高,由此可見,表冷器的傳熱溫差相對(duì)增大,傳熱效率提高。機(jī)器露點(diǎn)L1’溫度升高,則制冷效率提高。其處理過程與計(jì)算方法見表1。
一次回風(fēng)系統(tǒng)的冷負(fù)荷有新風(fēng)冷負(fù)荷Qx=Gx(hw-hN)、室內(nèi)冷負(fù)荷QS=G(hN-hO)、風(fēng)機(jī)冷負(fù)荷QF=G(hO-hS)、再熱冷負(fù)荷QZ=G(hS-hL)構(gòu)成。二次回風(fēng)系統(tǒng)冷負(fù)荷由新風(fēng)冷負(fù)荷、室內(nèi)冷負(fù)荷和風(fēng)機(jī)冷負(fù)荷構(gòu)成,與一次回風(fēng)相比,節(jié)省了再熱冷負(fù)荷。集中回風(fēng)型二次回風(fēng)與獨(dú)立回風(fēng)型二次回風(fēng)相比,冷負(fù)荷構(gòu)成相同。我們認(rèn)為,在設(shè)計(jì)工作中,用集中回風(fēng)型二次回風(fēng)的計(jì)算方法作為獨(dú)立回風(fēng)型二次回風(fēng)系統(tǒng)的簡(jiǎn)化計(jì)算,可以滿足實(shí)際運(yùn)行精度要求。
在冬季和接近冬季的過渡季節(jié),空調(diào)系統(tǒng)固定二次回風(fēng),空氣處理流程圖見圖2。新風(fēng)與一次回風(fēng)混合接著與二次回風(fēng)混合,經(jīng)盤管加熱,干蒸汽加濕送入室內(nèi)。
在本項(xiàng)目中采用了二次回風(fēng)系統(tǒng)設(shè)計(jì),根據(jù)室內(nèi)空氣處理過程,選空調(diào)機(jī)組總風(fēng)量25000m3/h,冷量90kW,風(fēng)機(jī)全壓600Pa,額定轉(zhuǎn)速960rpm,軸功率7.4kW,銘牌功率11kW。
節(jié)省再熱能耗:若采用一次回風(fēng)系統(tǒng),空氣處理至機(jī)器露點(diǎn)后,為滿足送風(fēng)溫差需經(jīng)再熱至21℃送風(fēng)狀態(tài)點(diǎn)。機(jī)器露點(diǎn)與送風(fēng)狀態(tài)點(diǎn)焓差6.48kJ/kg,空調(diào)機(jī)組所需總再熱量8.4kW。表冷器除承擔(dān)室內(nèi)冷負(fù)荷外,應(yīng)額外處理8.4kW冷量以免再熱量影響室內(nèi)設(shè)計(jì)參數(shù),表冷器承擔(dān)的額外冷負(fù)荷造成制冷機(jī)及水泵等增加電耗約2.1kW。故該一次回風(fēng)系統(tǒng)共增加能耗10.5kW。
以全年運(yùn)行時(shí)間600小時(shí)計(jì)算,二次回風(fēng)系統(tǒng)較一次回風(fēng)加再熱系統(tǒng)節(jié)電約6300kWh,約占全年空調(diào)總能耗的20%左右。
2.3還能進(jìn)一步節(jié)省能耗的措施
由于二次回風(fēng)系統(tǒng)屬于變風(fēng)量定溫差系統(tǒng),當(dāng)部分負(fù)荷時(shí),送風(fēng)量相應(yīng)減少,若采用變頻風(fēng)機(jī),節(jié)能量相當(dāng)可觀。根據(jù)風(fēng)機(jī)的相似律,當(dāng)實(shí)際運(yùn)行的轉(zhuǎn)速r與額定轉(zhuǎn)速rm不同時(shí),其實(shí)際功率N與額定功率Nm之間的關(guān)系為:
空調(diào)季節(jié)部分負(fù)荷下,空調(diào)機(jī)組應(yīng)按室內(nèi)工況調(diào)節(jié)運(yùn)行頻率。根據(jù)相關(guān)計(jì)算,全年空調(diào)運(yùn)行狀態(tài)中,負(fù)荷率超過90%的時(shí)間僅為6%,而負(fù)荷率30%~70%占全年運(yùn)行時(shí)間約60%??照{(diào)機(jī)組若工頻運(yùn)行全年耗電4440kWh,而根據(jù)全年冷負(fù)荷變化變頻運(yùn)行只需耗電約890kWh,全年可節(jié)約用電3550kWh,節(jié)電71%。
3結(jié)束語(yǔ)
(1) 采用二次回風(fēng)系統(tǒng),不僅可以避免二次回風(fēng)加熱,而且空調(diào)系統(tǒng)耗冷量也相應(yīng)降低,二次回風(fēng)的意義在于減少制冷負(fù)荷的裝機(jī)容量和相應(yīng)的配套設(shè)備容量。
(2) 二次回風(fēng)方案中經(jīng)過表冷器降溫、除濕的風(fēng)量比一次回風(fēng)少,而在表冷后與回風(fēng)再混合一次的辦法代替了部分再熱量,因而與一次回風(fēng)系統(tǒng)比,冷量和再熱量均減少,因而說二次回風(fēng)比一次回風(fēng)系統(tǒng)節(jié)能。另外,由于冷量的減少,表冷器的表冷面積降低許多,所配置的電機(jī)功率降低,空調(diào)機(jī)組的初投資有所減少。冷凍水量、熱水量的減少,機(jī)組耗電量減少,空調(diào)的運(yùn)行成本均相應(yīng)降低。
因此,合理應(yīng)用二次回風(fēng),可以使空調(diào)系統(tǒng)制冷負(fù)荷與運(yùn)行負(fù)荷同時(shí)降低。
二次回風(fēng)系統(tǒng)在設(shè)備選型及管路系統(tǒng)設(shè)計(jì)時(shí)應(yīng)注意以下方面:
(1)與一次回風(fēng)相比,二次回風(fēng)的表冷器處理的循環(huán)風(fēng)量和冷量發(fā)生變化,應(yīng)認(rèn)真做好表冷器的設(shè)計(jì)校核工作。
(2)集中回風(fēng)型二次回風(fēng)中,二次回風(fēng)立管上應(yīng)加定風(fēng)量閥,固定二次回風(fēng)比例。二次回風(fēng)系統(tǒng)宜在空氣處理機(jī)的一次回風(fēng)混合段、二次回風(fēng)混合段、送風(fēng)總管等處設(shè)溫濕度計(jì),以便監(jiān)控運(yùn)行狀況。
(3)風(fēng)機(jī)噪聲容易通過二次回風(fēng)管傳播,并且二次回風(fēng)立管的閥門容易產(chǎn)生哨音,所以應(yīng)在回風(fēng)總管加消聲器或者消聲彎頭,降低噪音對(duì)系統(tǒng)的影響。
參考文獻(xiàn)
1潔凈廠房設(shè)計(jì)規(guī)范.GB 50073-2001.中國(guó)計(jì)劃出版社
2電子工業(yè)部第十設(shè)計(jì)研究院.空氣調(diào)節(jié)設(shè)計(jì)手冊(cè).中國(guó)建筑工業(yè)出版社
3陸耀慶主編.實(shí)用供熱空調(diào)設(shè)計(jì)手冊(cè).中國(guó)建筑工業(yè)出版社
1.建筑節(jié)能設(shè)計(jì)
一些建設(shè)單位對(duì)建筑節(jié)能重要性及節(jié)能發(fā)展趨勢(shì)認(rèn)識(shí)不足,沒有站在建設(shè)資源節(jié)約型、環(huán)境友好型社會(huì)的高度認(rèn)識(shí)節(jié)能工作,尤其是一些開發(fā)商,無(wú)視國(guó)家強(qiáng)制性標(biāo)準(zhǔn),擅自更改已通過節(jié)能專項(xiàng)審查的節(jié)能設(shè)計(jì),降低節(jié)能標(biāo)準(zhǔn),為了應(yīng)付監(jiān)督機(jī)構(gòu)按節(jié)能規(guī)范要求的檢查,強(qiáng)令設(shè)計(jì)單位進(jìn)行設(shè)計(jì)變更,有的設(shè)計(jì)單位礙于建設(shè)單位的設(shè)計(jì)費(fèi)支付原因,隨意進(jìn)行設(shè)計(jì)變更,有的施工圖審查單位直接在設(shè)計(jì)變更上蓋審查章了事,監(jiān)理單位視而不見,一條違規(guī)鏈就此形成,基層監(jiān)督單位監(jiān)管力度有限,最終只能以竣工驗(yàn)收為砝碼被動(dòng)的制止相關(guān)責(zé)任主體的違規(guī)行為,筆者認(rèn)為應(yīng)該施工現(xiàn)場(chǎng)與建筑市場(chǎng)聯(lián)動(dòng),質(zhì)量監(jiān)督機(jī)構(gòu)加大對(duì)各責(zé)任主體不良行為的記錄,通報(bào)給上級(jí)建設(shè)主管部門進(jìn)行處罰。
2.資質(zhì)和施工人員管理
由于節(jié)能規(guī)范中沒有對(duì)節(jié)能施工資質(zhì)提出特殊要求,只要具備建筑工程承包的資質(zhì)就可承攬施工任務(wù),目前節(jié)能工程施工企業(yè)有總承包資質(zhì)、建筑裝飾裝修資質(zhì)、建筑防水資質(zhì),相當(dāng)一部分是是材料生產(chǎn)商直接施工,所以合同有總分包合同,也有供貨合同,雖然一些地方出臺(tái)了節(jié)能材料備案登記準(zhǔn)入制度的地方性規(guī)定,但是資質(zhì)和作業(yè)人員的良莠不齊還是給施工質(zhì)量埋下了隱患,根據(jù)節(jié)能規(guī)范規(guī)定施工單位施工前要對(duì)施工人員進(jìn)行交底和操作培訓(xùn),在檢查過程中交底記錄都有而且簽字齊全,實(shí)際上做了交底和培訓(xùn)的施工企業(yè)究竟有多少,不得而知,如果能及時(shí)出臺(tái)節(jié)能資質(zhì)管理相關(guān)規(guī)定,節(jié)能專業(yè)操作人員統(tǒng)一培訓(xùn)考核合格后上崗,或許能改變目前資質(zhì)和人員狀況。
3.節(jié)能工程施工、檢測(cè)與管理
3.1原材料檢驗(yàn)
新規(guī)范對(duì)建筑節(jié)能及檢測(cè)分為十個(gè)分項(xiàng)工程,檢測(cè)內(nèi)容近八十項(xiàng),如此之多的檢測(cè)內(nèi)容,加上市場(chǎng)的不公平競(jìng)爭(zhēng),承包單價(jià)偏低,一些分包單位為了降低成本,經(jīng)常減少檢驗(yàn)批次、簡(jiǎn)化檢測(cè)項(xiàng)目,主要表現(xiàn)在:
《規(guī)范》規(guī)定保溫材料、粘接材料、增強(qiáng)網(wǎng)、熱鍍鋅鋼絲同一廠家同一品種的產(chǎn)品,當(dāng)單位工程建筑面積在20000m2以下時(shí)各抽查不少于3次;當(dāng)單位工程建筑面積在20000m2以上時(shí)各抽查不少于6次,一些分包單位原材復(fù)試隨意做,進(jìn)場(chǎng)幾個(gè)批次做幾次,大多數(shù)分包商經(jīng)常是指定分包商,總包單位疏于管理,經(jīng)常達(dá)不到規(guī)范檢測(cè)要求。保溫系統(tǒng)粘接強(qiáng)度現(xiàn)場(chǎng)檢測(cè)后錨固件現(xiàn)場(chǎng)拉拔試驗(yàn),每個(gè)檢驗(yàn)批抽查不少于3處,每500~1000m2一個(gè)檢驗(yàn)批,按單體5000m2保溫計(jì)算,至少要做15處以上拉拔實(shí)驗(yàn),但是有些單位經(jīng)常只做3處,這種隨意減少檢驗(yàn)批次的做法,以概率統(tǒng)計(jì)的方法分析,根本反映不了施工的實(shí)際情況,像以上這種情況在節(jié)能分部工程驗(yàn)收及資料檢查中經(jīng)常遇到,一般的解決方法是要求施工單位補(bǔ)做原材檢驗(yàn)和加大實(shí)體鉆芯檢驗(yàn)數(shù)量。
對(duì)于建筑節(jié)能效果影響較大的部分材料和設(shè)備應(yīng)按《規(guī)范》規(guī)定實(shí)施抽樣復(fù)驗(yàn),以驗(yàn)證質(zhì)量是否符合要求。其復(fù)驗(yàn)數(shù)量、頻率和參數(shù)在規(guī)范中已都有規(guī)定。但是,由于目前我市對(duì)節(jié)能材料和設(shè)備的項(xiàng)目檢測(cè)能力有限,許多項(xiàng)目一時(shí)無(wú)法檢測(cè),例如散熱器單位散熱量和金屬熱強(qiáng)度等,而異地檢測(cè)必然會(huì)增加難度,因此在目前階段可區(qū)別對(duì)待處理。對(duì)于那些體量較大、比較重要的或擬創(chuàng)優(yōu)質(zhì)工程的項(xiàng)目,應(yīng)盡量按《規(guī)范》規(guī)定內(nèi)容進(jìn)行復(fù)驗(yàn),對(duì)于其他工程本市暫無(wú)法檢測(cè)的項(xiàng)目可暫不復(fù)驗(yàn)檢測(cè)。而如果對(duì)于產(chǎn)品或設(shè)備質(zhì)量有懷疑時(shí)則必須進(jìn)行復(fù)驗(yàn),暫時(shí)不進(jìn)行復(fù)驗(yàn)的材料和設(shè)備,應(yīng)由設(shè)計(jì)、施工、監(jiān)理、建設(shè)單位協(xié)商后以會(huì)議紀(jì)要形成文件,達(dá)成一致意見并報(bào)質(zhì)量監(jiān)督部門備案。
3.2隱蔽工程驗(yàn)收
《規(guī)范》對(duì)建筑節(jié)能工程施工中應(yīng)進(jìn)行隱蔽工程驗(yàn)收的部位和內(nèi)容都有詳細(xì)規(guī)定,當(dāng)施工中出現(xiàn)規(guī)范未列出內(nèi)容時(shí),則應(yīng)在施工組織設(shè)計(jì)或施工方案加以補(bǔ)充;隱蔽工程驗(yàn)收應(yīng)按施工工序進(jìn)度對(duì)隱蔽部位逐項(xiàng)分次驗(yàn)收,驗(yàn)收不僅應(yīng)有詳細(xì)文字記錄,還應(yīng)有必要的影像資料,影像資料必須與所驗(yàn)收的隱蔽工程密切聯(lián)系,必須真實(shí)且在驗(yàn)收時(shí)形成,并且影像資料應(yīng)有監(jiān)理單位簽字確認(rèn),這對(duì)后來的節(jié)能專項(xiàng)驗(yàn)收能提供很大的依據(jù),但是目前能按以上要求做的工程數(shù)量很有限,如果監(jiān)督機(jī)構(gòu)在節(jié)能工程實(shí)施前對(duì)責(zé)任主體各方做一個(gè)節(jié)能專項(xiàng)監(jiān)督交底,節(jié)能施工過程中加大巡查頻次,督促各方嚴(yán)格工序過程控制,以上問題還是可以避免的。
3.3建筑節(jié)能現(xiàn)場(chǎng)檢測(cè)
(1)外墻節(jié)能構(gòu)造現(xiàn)場(chǎng)實(shí)體檢驗(yàn)(鉆芯檢驗(yàn))
現(xiàn)場(chǎng)實(shí)體鉆芯檢驗(yàn)應(yīng)在監(jiān)理(建設(shè))人員見證下實(shí)施,可由施工單位實(shí)施,也可委托有資質(zhì)的檢測(cè)機(jī)構(gòu)實(shí)施。無(wú)論由施工單位實(shí)施還是由檢測(cè)機(jī)構(gòu)實(shí)施,檢測(cè)過程均須全程到場(chǎng)見證,且應(yīng)填寫見證記錄。檢測(cè)報(bào)告應(yīng)由檢測(cè)人員簽名并加蓋檢測(cè)實(shí)施單位公章。
(2)外窗氣密性實(shí)體檢測(cè)
根據(jù)《規(guī)范》要求,對(duì)已完成安裝的外窗在其使用位置應(yīng)進(jìn)行氣密性測(cè)試,檢驗(yàn)方法依據(jù)國(guó)家現(xiàn)行有關(guān)標(biāo)準(zhǔn),檢驗(yàn)?zāi)康氖浅闃域?yàn)證建筑外窗氣密性是否符合節(jié)能設(shè)計(jì)要求和國(guó)家現(xiàn)行有關(guān)標(biāo)準(zhǔn),但是現(xiàn)在部分施工單位的外窗氣密性檢測(cè)是在實(shí)驗(yàn)室里完成的,對(duì)于此類現(xiàn)象要加強(qiáng)對(duì)監(jiān)理單位的監(jiān)管,要求監(jiān)理人員必須做到現(xiàn)場(chǎng)見證檢測(cè),加大對(duì)檢測(cè)機(jī)構(gòu)的監(jiān)督管理,嚴(yán)懲隨意出具虛假檢測(cè)報(bào)告的行為。
(3)節(jié)能性能檢測(cè)
關(guān)鍵詞綜合能效比EER;冷水機(jī)組;空調(diào)系統(tǒng)能耗
Abstract: This project is a renovation project of a five Stars Hotel, the relevant provisions on energy requirements, the annual average energy efficiency of the air conditioning system than EER need to reach more than 5.4, to reach the effect of energy saving. This paper aims to introduce how to make reasonable selection of chillers, terminal equipment selection and piping requirements and to meet the requirements prescribed energy.
Key words comprehensive energy efficiency than EER; chiller; energy consumption of air conditioning system
中圖分類號(hào):TB494文獻(xiàn)標(biāo)識(shí)碼:A文章編碼:
一、項(xiàng)目概況
本工程的冷源機(jī)房設(shè)計(jì)有3臺(tái)700RT的離心式冷水機(jī)組(2用1備),2臺(tái)350RT的離心式冷水機(jī)組,7臺(tái)冷凍水泵(L=145m3/h、18.5Kw,6用1備),7臺(tái)冷卻水泵(L=292m3/h、30Kw,6用1備),8臺(tái)冷卻塔(L=300m3/h、7.5Kw,6用2備)。
冷凍水采用大溫差設(shè)計(jì)進(jìn)出水溫為15℃/7℃,冷卻水進(jìn)出水溫為32℃/37℃。設(shè)計(jì)要求滿負(fù)荷空調(diào)主機(jī)房冷源系統(tǒng)制冷綜合能效比EER設(shè)計(jì)值須不低于4.88,全年實(shí)測(cè)制冷綜合能效比EER值不低于5.4。
1、滿負(fù)荷EER計(jì)算要求
設(shè)計(jì)要求滿負(fù)荷空調(diào)主機(jī)房冷源系統(tǒng)制冷綜合能效比EER設(shè)計(jì)值不低于4.88,即:
計(jì)算公式:EER總1=Q總冷量 /N總 (設(shè)計(jì)工況)
N總=N1+N2+N3+N4
式中:
Q總冷量1=2100RT×3.5169=7385.5KW(設(shè)計(jì)工況滿負(fù)荷為2100RT)
N總1:滿負(fù)荷空調(diào)主機(jī)房冷源系統(tǒng)制冷電功率。
N1:冷水機(jī)組合在設(shè)計(jì)工況下,共輸出2100RT冷量時(shí)的實(shí)際電功率之和。
N2:冷凍水泵組在設(shè)計(jì)工況下,冷水機(jī)組輸出2100RT冷量時(shí)的對(duì)應(yīng)冷凍水流量時(shí)的實(shí)際電功率之和(KW)。
N3:冷卻水泵組在設(shè)計(jì)工況下,冷水機(jī)組輸出2100RT冷量時(shí)的對(duì)應(yīng)冷卻水流量時(shí)的實(shí)際電功率之和(KW)。
N4:冷卻塔組合在設(shè)計(jì)工況下,冷水機(jī)組輸出2100RT冷量時(shí)的對(duì)應(yīng)冷卻塔組合的實(shí)際電功率之和(KW)。
2、全年制冷綜合能效比EER計(jì)算要求
按項(xiàng)目實(shí)際的負(fù)荷情況,保證空調(diào)冷熱源主機(jī)房系統(tǒng)在全年實(shí)測(cè)制冷綜合能效比EER值不低于5.4,即
計(jì)算公式:EER總2=Q總冷量2 /N總 2 (全年)
N總2=N1’+N2’+N3’+N4’
式中:
Q總冷量2: 全年主機(jī)房冷凍水輸出冷量計(jì)量表讀數(shù)(實(shí)際測(cè)量值累計(jì)之和KW*h)。
N1’:冷水機(jī)組的計(jì)量電表度數(shù)(實(shí)際測(cè)量值全年累計(jì)之和KW*h)。
N2’:冷凍水泵組合的計(jì)量電表度數(shù)(實(shí)際測(cè)量值全年累計(jì)之和KW*h)。
N3’:冷卻水泵組合的計(jì)量電表度數(shù)(實(shí)際測(cè)量值全年累計(jì)之和KW*h)。
N4’:冷卻塔組合的計(jì)量電表度數(shù)(實(shí)際測(cè)量值全年累計(jì)之和KW*h)。
二、需求分析
1、設(shè)備功率情況
按設(shè)計(jì)要求離心式和螺桿式冷水機(jī)組COP≥6.1,按COP=6.1初步計(jì)算出設(shè)備功率在總共功率的占比情況:
【表1】
2、設(shè)備效率分析
從表1可以看出,冷水機(jī)組的功率占總功率比達(dá)到78.27%,即冷水機(jī)組的效率對(duì)全年制冷綜合能效比EER值影響最大。由于螺桿冷水機(jī)組的效率普遍不高,負(fù)荷率占比低,所以離心式冷水機(jī)組的效率對(duì)EER的影響最大。
而冷凍水泵、冷卻水泵、冷卻塔的效率小計(jì)為21.63%,且采用變頻運(yùn)行,所以其設(shè)備效率對(duì)EER影響不大,其中值得注意的是冷卻塔的回水溫度對(duì)冷水機(jī)組的效率影響很大。
3、滿負(fù)荷EER分析
查各品牌的冷水機(jī)組可以知道,冷凍水流量平均為265 m3/h左右,冷卻水流量平均為250 m3/h左右,結(jié)合流量情況代入水泵運(yùn)行曲線:
冷凍水泵在冷水機(jī)組滿負(fù)荷時(shí)功率為:16.6Kw/臺(tái),小計(jì)99.6Kw;
冷卻水泵在冷水機(jī)組滿負(fù)荷時(shí)功率為:26.4Kw/臺(tái),小計(jì)158.4Kw。
由此推算出,當(dāng)主機(jī)國(guó)標(biāo)工況效率COP達(dá)到6.1時(shí),
滿負(fù)荷EER=2100RT×3.5169/1509Kw=4.89,滿足要求。
所以研發(fā)的重點(diǎn)在于:如何選擇離心式冷水機(jī)組來確保全年制冷綜合能效比EER值達(dá)到要求。
三、冷水機(jī)組單機(jī)運(yùn)行特性
【表2】離心式冷水機(jī)組運(yùn)行特性曲線
注:曲線代表不同溫度冷卻水和不同負(fù)荷時(shí)的COP。
由表2可以看出,離心式冷水機(jī)組的效率COP會(huì)根據(jù)負(fù)荷、冷卻水溫度的變化而變化。并非負(fù)荷越高效率越高,但冷卻水溫越低效率越高。所以冷水機(jī)組,特別是離心式冷水機(jī)組的設(shè)計(jì)工況的能效比(COP值)和設(shè)計(jì)工況綜合部分負(fù)荷能效(NPLV值)對(duì)本項(xiàng)目節(jié)能研發(fā)的重要要素。
四、建立環(huán)境模型
根據(jù)離心冷水機(jī)組的效率由負(fù)荷和冷卻水溫而影響,所以根據(jù)負(fù)荷和冷卻水溫建立本項(xiàng)目節(jié)能的環(huán)境模型。
根據(jù)2010年項(xiàng)目原冷凍機(jī)房的耗電數(shù)據(jù),分析出項(xiàng)目每個(gè)月份的空調(diào)負(fù)荷。另外,從“中國(guó)氣象科學(xué)數(shù)據(jù)共享服務(wù)網(wǎng)”1971~2000年數(shù)據(jù)得每個(gè)月的干球溫度和相對(duì)濕度,由兩者可計(jì)算得出每個(gè)月的濕球溫度,冷卻回水溫度可在此溫度上加4℃~5℃,由于節(jié)能要求較高,本工程保守取5℃。由以上兩項(xiàng)數(shù)據(jù)建立的模型如下:
【表3】
五、機(jī)組選型模型
1、根據(jù)環(huán)境模型編制計(jì)算表,如下表
【表4】
注:設(shè)備除冷凍主機(jī)、水泵、冷卻塔外,還需考慮要考慮冷凍機(jī)房輔助設(shè)備,如冷凍油、變頻器、電動(dòng)閥、水處理等的電量。
2、計(jì)算說明
(1)考慮到螺桿機(jī)組的效率偏低,在某范圍負(fù)荷內(nèi)可以允許同時(shí)開3臺(tái)離心主機(jī),而非備用一臺(tái)離心主機(jī)不啟動(dòng)。
(2)根據(jù)主機(jī)最優(yōu)的開機(jī)策略,確定在部分負(fù)荷下,每臺(tái)主機(jī)所承擔(dān)的負(fù)荷,再根據(jù)當(dāng)月的冷卻水溫度和廠家提供的資料參數(shù),使用以下公式計(jì)算每臺(tái)主機(jī)的輸入功率。
【關(guān)鍵詞】工業(yè);固定資產(chǎn)投資;節(jié)能;評(píng)估
一、引言
2010年9月,根據(jù)《中華人民共和國(guó)節(jié)約能源法》和國(guó)務(wù)院一系列文件精神,國(guó)家發(fā)展改革委了《固定資產(chǎn)投資項(xiàng)目節(jié)能評(píng)估和審查暫行辦法》(以下簡(jiǎn)稱“《辦法》”),并于11月1日正式實(shí)施?!掇k法》把節(jié)能審查作為項(xiàng)目審批、核準(zhǔn)或開工建設(shè)的前置性條件以及項(xiàng)目設(shè)計(jì)、施工和竣工驗(yàn)收的重要依據(jù)?!掇k法》的出臺(tái),一方面能夠約束新上項(xiàng)目落實(shí)有關(guān)節(jié)能法規(guī)、標(biāo)準(zhǔn),不斷提高能源利用效率;另一方面能夠與能源消耗總量控制相結(jié)合,從源頭上遏制能耗不合理增長(zhǎng)。由于固定資產(chǎn)投資項(xiàng)目節(jié)能評(píng)估和審查工作剛剛起步,各地區(qū)、各部門,相關(guān)機(jī)構(gòu)和人員對(duì)能評(píng)工作會(huì)有一個(gè)逐步了解和熟悉的過程,目前還處于摸索階段。鑒于工業(yè)項(xiàng)目在固定資產(chǎn)投資中比重較大,現(xiàn)就工業(yè)固定資產(chǎn)投資項(xiàng)目節(jié)能評(píng)估的程序、內(nèi)容和方法做以下探討。
二、節(jié)能評(píng)估程序
項(xiàng)目節(jié)能評(píng)估機(jī)構(gòu)開展節(jié)能評(píng)估的主要工作程序包括:簽訂評(píng)估合同或協(xié)議、組建節(jié)能評(píng)估工作小組、開展節(jié)能評(píng)估、完善節(jié)能評(píng)估文件。
1.簽訂評(píng)估合同或協(xié)議。合同或協(xié)議書中應(yīng)清晰描述項(xiàng)目的節(jié)能評(píng)估內(nèi)容、要求、工作條件、費(fèi)用支付、風(fēng)險(xiǎn)責(zé)任以及與之相關(guān)的技術(shù)和法律等問題。特別需要注意的是,節(jié)能評(píng)估機(jī)構(gòu)要盡量避免由于對(duì)業(yè)務(wù)環(huán)境的復(fù)雜程度判斷失誤或不慎,或評(píng)估機(jī)構(gòu)對(duì)自身的業(yè)務(wù)勝任能力估計(jì)過高等原因,簽訂了超過自身業(yè)務(wù)能力范圍的契約而產(chǎn)生的風(fēng)險(xiǎn)。如評(píng)估機(jī)構(gòu)為了承攬業(yè)務(wù),先簽約再考核業(yè)務(wù)環(huán)境,導(dǎo)致評(píng)估成本過高,或造成評(píng)估報(bào)告的嚴(yán)重高風(fēng)險(xiǎn)等。
2.組建節(jié)能評(píng)估工作小組。接受項(xiàng)目建設(shè)單位委托后,評(píng)估機(jī)構(gòu)應(yīng)根據(jù)項(xiàng)目特點(diǎn),組建專業(yè)齊備、能力合格、工程經(jīng)驗(yàn)豐富的評(píng)估團(tuán)隊(duì)。評(píng)估團(tuán)隊(duì)?wèi)?yīng)覆蓋項(xiàng)目所屬行業(yè)的各工藝專業(yè),以及熱能、電氣和技術(shù)經(jīng)濟(jì)等節(jié)能評(píng)估工作所需專業(yè)。評(píng)估人員原則上應(yīng)具有相應(yīng)的專業(yè)技術(shù)資格,熟悉節(jié)能評(píng)估工作的內(nèi)容深度要求、技術(shù)規(guī)范、評(píng)價(jià)標(biāo)準(zhǔn)和程序方法等,具備分析和評(píng)估項(xiàng)目能源利用狀況,提出有效節(jié)能措施,核算項(xiàng)目能源消費(fèi)總量,判斷項(xiàng)目能效水平等專業(yè)能力。項(xiàng)目節(jié)能評(píng)估期間,評(píng)估團(tuán)隊(duì)?wèi)?yīng)保持人員穩(wěn)定。
3.開展節(jié)能評(píng)估。主要工作包括收集項(xiàng)目資料、確定評(píng)估體系和評(píng)估范圍、評(píng)估項(xiàng)目情況、形成評(píng)估結(jié)論、編制評(píng)估文件等。年綜合能源消費(fèi)量在5000噸標(biāo)準(zhǔn)煤(等價(jià)值)以上的項(xiàng)目,應(yīng)分專業(yè)評(píng)估并相互會(huì)簽。評(píng)估期間,節(jié)能評(píng)估機(jī)構(gòu)應(yīng)與項(xiàng)目建設(shè)單位、可研編制單位等充分溝通。編制完成后的節(jié)能評(píng)估文件應(yīng)分別加蓋節(jié)能評(píng)估機(jī)構(gòu)和項(xiàng)目建設(shè)單位公章,由項(xiàng)目建設(shè)單位報(bào)送節(jié)能審查。
4.完善節(jié)能評(píng)估文件。節(jié)能評(píng)估文件報(bào)送節(jié)能審查后,節(jié)能評(píng)估機(jī)構(gòu)應(yīng)組織各專業(yè)人員參加評(píng)審會(huì),交流項(xiàng)目評(píng)估情況等,并根據(jù)節(jié)能評(píng)審和審查階段所提意見,及時(shí)對(duì)評(píng)估文件進(jìn)行修改和完善。
三、節(jié)能評(píng)估內(nèi)容
1.評(píng)估依據(jù)。相關(guān)法律、法規(guī)、規(guī)劃、行業(yè)準(zhǔn)入條件、產(chǎn)業(yè)政策,相關(guān)標(biāo)準(zhǔn)及規(guī)范,節(jié)能技術(shù)、產(chǎn)品推薦目錄,國(guó)家明令淘汰的用能產(chǎn)品、設(shè)備、生產(chǎn)工藝等目錄,以及相關(guān)工程資料和技術(shù)合同等。
2.項(xiàng)目概況。(1)建設(shè)單位基本情況。建設(shè)單位名稱、性質(zhì)、地址、郵編、法人代表、項(xiàng)目聯(lián)系人及聯(lián)系方式,企業(yè)運(yùn)營(yíng)總體情況。(2)項(xiàng)目基本情況。項(xiàng)目名稱、建設(shè)地點(diǎn)、項(xiàng)目性質(zhì)、建設(shè)規(guī)模及內(nèi)容、項(xiàng)目工藝方案、總平面布置、主要經(jīng)濟(jì)技術(shù)指標(biāo)、項(xiàng)目進(jìn)度計(jì)劃等(改、擴(kuò)建項(xiàng)目需對(duì)項(xiàng)目原基本情況進(jìn)行說明)。(3)項(xiàng)目用能概況:主要供、用能系統(tǒng)與設(shè)備的初步選擇,能源消耗種類、數(shù)量及能源使用分布情況(改、擴(kuò)建項(xiàng)目需對(duì)項(xiàng)目原用能情況及存在的問題進(jìn)行說明)。
3.能源供應(yīng)情況分析評(píng)估。(1)項(xiàng)目所在地能源供應(yīng)條件及消費(fèi)情況;(2)項(xiàng)目能源消費(fèi)對(duì)當(dāng)?shù)啬茉聪M(fèi)的影響。
4.項(xiàng)目建設(shè)方案節(jié)能評(píng)估。(1)項(xiàng)目選址、總平面布置對(duì)能源消費(fèi)的影響;(2)項(xiàng)目工藝流程、技術(shù)方案對(duì)能源消費(fèi)的影響;(3)主要用能工藝和工序,及其能耗指標(biāo)和能效水平;(4)主要耗能設(shè)備,及其能耗指標(biāo)和能效水平;(5)輔助生產(chǎn)和附屬生產(chǎn)設(shè)施及其能耗指標(biāo)和能效水平。
5.項(xiàng)目能源消耗及能效水平評(píng)估。(1)項(xiàng)目能源消費(fèi)種類、來源及消費(fèi)量分析評(píng)估;(2)能源加工、轉(zhuǎn)換、利用情況(可采用能量平衡表)分析評(píng)估;(3)能效水平分析評(píng)估。包括單位產(chǎn)品(產(chǎn)值)綜合能耗、可比能耗,主要工序(藝)單耗,單位建筑面積分品種實(shí)物能耗和綜合能耗,單位投資能耗等。
6.節(jié)能措施評(píng)估。(1)節(jié)能措施。一是節(jié)能技術(shù)措施:生產(chǎn)工藝、動(dòng)力、建筑、給排水、暖通與空調(diào)、照明、控制、電氣等方面的節(jié)能技術(shù)措施,包括節(jié)能新技術(shù)、新工藝、新設(shè)備應(yīng)用,余熱、余壓、可燃?xì)怏w回收利用,建筑圍護(hù)結(jié)構(gòu)及保溫隔熱措施,資源綜合利用,新能源和可再生能源利用等。二是節(jié)能管理措施:節(jié)能管理制度和措施,能源管理機(jī)構(gòu)及人員配備,能源統(tǒng)計(jì)、監(jiān)測(cè)及計(jì)量?jī)x器儀表配置等。(2)單項(xiàng)節(jié)能工程。未納入建設(shè)項(xiàng)目主導(dǎo)工藝流程和擬分期建設(shè)的節(jié)能工程,詳細(xì)論述工藝流程、設(shè)備選型、單項(xiàng)工程節(jié)能量計(jì)算、單位節(jié)能量投資、投資估算及投資回收期等。(3)節(jié)能措施效果評(píng)估。節(jié)能措施節(jié)能量測(cè)算,單位產(chǎn)品(建筑面積)能耗、主要工序(藝)能耗、單位投資能耗等指標(biāo)國(guó)際國(guó)內(nèi)對(duì)比分析,設(shè)計(jì)指標(biāo)是否達(dá)到同行業(yè)國(guó)內(nèi)先進(jìn)水平或國(guó)際先進(jìn)水平。(4)節(jié)能措施經(jīng)濟(jì)性評(píng)估。節(jié)能技術(shù)和管理措施的成本及經(jīng)濟(jì)效益測(cè)算和評(píng)估。
7.存在問題及建議。
8.結(jié)論。
9.附圖、附表。廠(場(chǎng))區(qū)總平面圖、車間工藝平面布置圖;主要耗能設(shè)備一覽表;主要能源和耗能工質(zhì)品種及年需求量表;能量平衡表等。
四、節(jié)能評(píng)估方法
1.組建評(píng)估小組,進(jìn)行任務(wù)分工。簽訂節(jié)能評(píng)估合同后,首先要組建評(píng)估小組,進(jìn)行任務(wù)分工,必須責(zé)任到人。由于節(jié)能評(píng)估是在項(xiàng)目投資決策前對(duì)項(xiàng)目能源利用科學(xué)性、合理性的評(píng)估,不僅專業(yè)性較強(qiáng),而且政策性也較強(qiáng),因此,評(píng)估小組的專家不僅要求對(duì)本行業(yè)國(guó)內(nèi)外先進(jìn)的工藝技術(shù)、設(shè)備,特別是先進(jìn)的能源利用、資源綜合利用技術(shù)非常熟悉,同時(shí)還要求具備較強(qiáng)的政策敏銳性。
2.收集項(xiàng)目相關(guān)資料。收集項(xiàng)目基本情況及用能方面的相關(guān)資料,主要包括:(1)建設(shè)單位基本情況。如建設(shè)單位名稱、性質(zhì)、地址、郵編、法人代表、項(xiàng)目聯(lián)系人及聯(lián)系方式,企業(yè)運(yùn)營(yíng)總體情況等。(2)項(xiàng)目基本情況:如項(xiàng)目名稱、建設(shè)地點(diǎn)(包括位于或接近的主要交通線)、項(xiàng)目性質(zhì)、投資規(guī)模及建設(shè)內(nèi)容、項(xiàng)目工藝方案、總平面布置、主要經(jīng)濟(jì)技術(shù)指標(biāo)、項(xiàng)目進(jìn)度計(jì)劃,改、擴(kuò)建項(xiàng)目原項(xiàng)目的基本情況,改、擴(kuò)建項(xiàng)目的評(píng)估范圍等。(3)項(xiàng)目用能情況:如項(xiàng)目能源消耗種類、數(shù)量及能源使用分布情況,項(xiàng)目主要供、用能系統(tǒng)與設(shè)備的選擇,改、擴(kuò)建項(xiàng)目要分析原項(xiàng)目用能情況及存在的問題等。(4)項(xiàng)目所在地的氣候區(qū)屬及其主要特征:如年平均氣溫(最冷月和最熱月)、制冷度日數(shù)、采暖度日數(shù)、極端氣溫與月平均氣溫、日照率等。(5)項(xiàng)目所在地的經(jīng)濟(jì)、社會(huì)和能源供應(yīng)、消費(fèi)概況:如經(jīng)濟(jì)發(fā)展現(xiàn)狀、節(jié)能目標(biāo)、能源供應(yīng)和消費(fèi)現(xiàn)狀、重點(diǎn)耗能企業(yè)分布及其能源供應(yīng)消費(fèi)特點(diǎn)、交通運(yùn)輸概況等。當(dāng)現(xiàn)有資料無(wú)法完整準(zhǔn)確反映項(xiàng)目概況時(shí),可進(jìn)行現(xiàn)場(chǎng)勘察、調(diào)查和測(cè)試?,F(xiàn)狀調(diào)查中,對(duì)與節(jié)能評(píng)估工作密切相關(guān)的內(nèi)容(如能源供應(yīng)、消費(fèi)、加工轉(zhuǎn)換和運(yùn)輸?shù)龋瑧?yīng)在現(xiàn)狀調(diào)查中注意收集全面詳細(xì)的信息,并盡可能提供定量數(shù)據(jù)和圖表。如需采用類比分析法,應(yīng)按上述要求全面獲取類比工程相關(guān)信息。
3.確定評(píng)估依據(jù)。根據(jù)項(xiàng)目實(shí)際情況收集相關(guān)資料并確定項(xiàng)目節(jié)能評(píng)估依據(jù),主要包括:(1)相關(guān)法律、法規(guī)、規(guī)劃、行業(yè)準(zhǔn)入條件、產(chǎn)業(yè)政策等。(2)相關(guān)標(biāo)準(zhǔn)及規(guī)范(國(guó)家標(biāo)準(zhǔn)、地方標(biāo)準(zhǔn)或相關(guān)行業(yè)標(biāo)準(zhǔn)均適用時(shí),執(zhí)行其中較嚴(yán)格的標(biāo)準(zhǔn))。(3)節(jié)能工藝、技術(shù)、裝備、產(chǎn)品等推薦目錄,國(guó)家明令淘汰的用能產(chǎn)品、設(shè)備、生產(chǎn)工藝等目錄。(4)項(xiàng)目環(huán)境影響評(píng)價(jià)、土地預(yù)審等相關(guān)資料、項(xiàng)目申請(qǐng)報(bào)告、可行性研究報(bào)告等立項(xiàng)資料。節(jié)能評(píng)估文件應(yīng)與各項(xiàng)評(píng)估依據(jù)有關(guān)內(nèi)容進(jìn)行對(duì)比,并給出評(píng)價(jià)結(jié)論。
4.選擇評(píng)估方法。通用的主要評(píng)估方法包括標(biāo)準(zhǔn)對(duì)照法、類比分析法、專家判斷法等。在實(shí)際評(píng)估工作開展過程中,可根據(jù)項(xiàng)目特點(diǎn)選擇適用的評(píng)估方法,可以采用一種評(píng)估方法也可綜合運(yùn)用多種評(píng)估方法。(1)標(biāo)準(zhǔn)對(duì)照法。是指通過對(duì)照相關(guān)節(jié)能法律法規(guī)、政策、技術(shù)標(biāo)準(zhǔn)和規(guī)范,對(duì)項(xiàng)目的能源利用是否科學(xué)合理進(jìn)行分析評(píng)估。評(píng)估要點(diǎn)包括:項(xiàng)目建設(shè)方案與節(jié)能規(guī)劃、相關(guān)行業(yè)準(zhǔn)入條件對(duì)比;項(xiàng)目平面布局、生產(chǎn)工藝、用能情況等建設(shè)方案與相關(guān)節(jié)能設(shè)計(jì)標(biāo)準(zhǔn)對(duì)比;主要用能設(shè)備與能效標(biāo)準(zhǔn)對(duì)比;項(xiàng)目單位產(chǎn)品能耗與相關(guān)能耗限額等標(biāo)準(zhǔn)對(duì)比等。(2)類比分析法。是指在缺乏相關(guān)標(biāo)準(zhǔn)規(guī)范的情況下,通過與處于同行業(yè)領(lǐng)先節(jié)能水平的既有工程進(jìn)行對(duì)比,分析判斷所評(píng)估項(xiàng)目的能源利用是否科學(xué)合理。類比分析法應(yīng)判斷所參考的類比工程能效水平是否達(dá)到國(guó)際先進(jìn)或國(guó)內(nèi)領(lǐng)先水平。評(píng)估要點(diǎn)可參照標(biāo)準(zhǔn)對(duì)照法。(3)專家判斷法。是指在沒有相關(guān)標(biāo)準(zhǔn)和類比工程的情況下,利用專家經(jīng)驗(yàn)、知識(shí)和技能,對(duì)項(xiàng)目能源利用是否科學(xué)合理進(jìn)行分析判斷的方法。采用專家判斷法,應(yīng)從生產(chǎn)工藝、用能情況、用能設(shè)備等方面,對(duì)項(xiàng)目的能源使用做出全面分析和計(jì)算,專家組成員的意見應(yīng)作為結(jié)論附件。
5.項(xiàng)目節(jié)能評(píng)估。項(xiàng)目節(jié)能評(píng)估包括能源供應(yīng)情況評(píng)估、項(xiàng)目設(shè)計(jì)方案節(jié)能評(píng)估、項(xiàng)目能源消費(fèi)和能效水平評(píng)估、節(jié)能措施評(píng)估等工作,其目的是對(duì)項(xiàng)目的用能狀況進(jìn)行全面分析,作為評(píng)估結(jié)論的重要依據(jù)。當(dāng)項(xiàng)目可行性研究報(bào)告等技術(shù)文件中記載的資料、數(shù)據(jù)等能夠滿足節(jié)能評(píng)估的需要和精度要求時(shí),應(yīng)通過復(fù)核校對(duì)后引用。對(duì)于能源消費(fèi)量、產(chǎn)品單耗、能源利用效率、節(jié)能效益等可定量表述的內(nèi)容,應(yīng)通過分析、測(cè)算(核算)給出定量結(jié)果。測(cè)算(核算)過程應(yīng)清晰,要符合現(xiàn)行統(tǒng)計(jì)方法制度及相關(guān)標(biāo)準(zhǔn)規(guī)定。如屬改、擴(kuò)建工程,應(yīng)分析原有主要生產(chǎn)工藝、用能工藝、主要耗能設(shè)備的用能情況及存在問題,以及項(xiàng)目實(shí)施后對(duì)原用能情況的改善作用。
6.編制節(jié)能評(píng)估文件。節(jié)能評(píng)估文件應(yīng)全面真實(shí)地反映節(jié)能評(píng)估的全部工作,文字應(yīng)簡(jiǎn)潔、準(zhǔn)確,論點(diǎn)明確,便于閱讀和審查。原始數(shù)據(jù)、主要計(jì)算過程等可編入正文或附錄;所參考的主要文獻(xiàn)按引用時(shí)間次序列出目錄;應(yīng)盡量采用圖表和照片等多種方式進(jìn)行表述。節(jié)能評(píng)估文件報(bào)送節(jié)能審查后,節(jié)能評(píng)估機(jī)構(gòu)應(yīng)組織各專業(yè)人員參加評(píng)審會(huì),交流項(xiàng)目評(píng)估情況等,并根據(jù)節(jié)能評(píng)審和審查階段所提意見,及時(shí)對(duì)評(píng)估文件進(jìn)行修改和完善。
節(jié)能環(huán)保方案 節(jié)能降耗案例 節(jié)能改造技術(shù) 節(jié)能環(huán)保 節(jié)能節(jié)電的重要性 節(jié)能工作意見 節(jié)能論文 節(jié)能減排 節(jié)能減排技術(shù) 節(jié)能與環(huán)保 紀(jì)律教育問題 新時(shí)代教育價(jià)值觀